Well pump · cycle protection

WellMate pressure-tank sizing

Size drawdown first, then tank volume. This prevents the common mistake of treating a tank’s nominal volume as the water delivered between pump starts.

Cutaway illustration of a composite pressure tank and well pump
1 · Pump duty
2 · Pressure switch

Recommended catalogue model

WM-14WB

V = D ÷ f
Minimum nominal tank volume161.8LSelected model capacity: 178 L
Required drawdown50.0 LQ × minimum runtime
Usable-volume factor0.309at selected pressures
No-demand refill / run time1.11 min55.0 L calculated drawdown

What it means:

The trap

A 178 L tank does not deliver 178 L per cycle.

Compressed air occupies most of the vessel. Between 30 and 50 psi, a WM-14WB publishes about 55.3 L drawdown. The calculator recomputes drawdown for your selected pressures.

D = max(pump flow × runtime, reserve)f = (cut-out − cut-in) ÷ (cut-out + atmospheric)Minimum tank volume = D ÷ f

Worked example · 3 m³/h

WM-14WB

A 3 m³/h pump delivers 50 L/min. One minute requires 50 L drawdown. At 2.07/3.45 bar, f = 0.309 and minimum nominal volume is 161.8 L. WM-12 is too small; 178 L WM-14WB gives about 55 L and 1.1 minutes.

  1. Use measured pump delivery at operating pressure.
  2. With pump power off and the tank fully drained, set air-cell precharge 4 psi (0.28 bar) below cut-in.
  3. Install a correctly sized relief valve that cannot be isolated from the tank.
  4. Not for VFD/constant-pressure sizing.

Check the assumptions

Method and primary references

The equations are shown so the result can be checked. Product data and site conditions still govern final selection.