Ion exchange · capacity and flow
Industrial water-softener sizing
Solve both sides of the problem: resin capacity for the hardness load and resin volume for the peak hydraulic flow. The larger result controls.
Controlling resin volume
Capacity controls
Design note:
Two limits, one answer
Capacity gets you through the run; flow gets you through the peak.
The answer is per online duty bed. In alternating duplex service, each vessel is sized for the full peak and the second is ready while the first regenerates.
What this does not decide
The resin datasheet and water analysis still govern.
- Account for iron, manganese, TDS, temperature and fouling.
- Verify valve service/backwash/brine flows and injector.
- Select simplex, alternating duplex or parallel duty for continuity.
- Use the selected resin’s actual salt-efficiency curve.
Check the assumptions
Method and primary references
The equations are shown so the result can be checked. Product data and site conditions still govern final selection.
- Purolite C100 Sodium CycleManufacturer operating-capacity and regeneration guidance.
- DuPont Water Conditioning ManualIon-exchange design, flow and capacity background.